Constant Wattage Medium Temperature Heating Cable CWM 8-1CTChromalox CWM constant wattage heating cable is a proven, reliable solution for industrial process temperature maintenance and freeze protection. CWM features a parallel heating core that produces uniform thermal output over its entire length. Using a small power point, you can easily configure and install a heat tracing system as short as several feet or as long as 780 feet right in the field. With 392°F (200°C) fluoropolymer electrical insulation over-jacketing, CWM has outstanding electrical and thermal properties, and is well suited for most chemically hostile environments. NOTE: A single quantity purchase equals 1ft of cable. Adding multiple
quantity of the same cable will add to the overall length of the
product.
For example: quantity of 10 = 10ft long cable.
NAME
|
Constant Wattage Heating Cable
...
|
APPROX. SIZE
|
0.300in
W x 0.250in H
/ 7.620mm W x 6.35mm H
|
Part#
|
392163 |
PROCESS TEMP MAINTENANCE
|
325ºF/163ºC
|
Agency Approval
|
CSA/UL Listed
|
MAXIMUM CONT TEMP, POWER OFF
|
392ºF/200ºC
|
VOLTS
|
120V
|
WATTS/FT
|
8W/FT
|
CABLE CONSTRUCTION
|
Twin 12 AWG Copper Buss Wire
|
HEATING CABLE LENGTH
|
Sold per Linear Foot, 1FT =1QTY
|
COLOR
|
Metallic
|
CONDUCTOR MATERIAL
|
Copper
|
MINIMUM BEND RADIUS
|
1.250in
/ 31.750mm
|
Applications
- Uniform Thermal Output, Low Energy Cost
- For Use on Metallic Pipes (Consult factory for Use on Plastic Pipes)
- No inrush at Any Ambient
- Industrial/Process and Commercial/Construction Applications
FEATURES - Durable, non-aging fluoropolymer jacket ensures long service life and can be used in some hostile environment
- Flexible, easy to install on most equipment and delivers long-term reliable performance
- Accurate temperature, reliable electric heat that can be consistently controlled and easily monitored
- Parallel circuitry allows cut-to-length
- Low profile, uses standard size thermal insulation on piping and process equipment
- Eliminates the need for oversized wiring or switchgear
- High performance, rated to withstand up to 392°F saturated steam (190 psig) temperature
CONSTRUCTIONS - Twin 12 AWG Copper Buss Wire - Provide reliable electrical current capability
- FEP Insulation Jacket – Electrically insulates buss wires
- Pairing Jacket – Secures two buss wires together and provides wrapping surface for Nichrome wire
- Nickel Chromium Wire – Heating component of cable
- FEP Insulation – Rugged outer sheath protects heating cable, assures longer service life
- Tinned Copper Braid – Plated copper braid increases robust construction, provides ground path and provides additional protection in any location
- FEP Overjacket – Fluoropolymer overjacket, over the braid, provides protection from most aqueous and chemically corrosive solutions
WARNING - A ground fault protection device is required by NEC to minimize the danger of fire if the heating cable is damaged or improperly installed. A minimum trip level of 30mA is recommended to minimize nuisance tripping
Approvals:
CSA Certified for ordinary areas UL Listed for ordinary areas
- Class I, Div. 2, Groups A, B, C, D
- Class II, Div. 2, Groups F, G. Rated T3 Temperature Class
|
|
 |